The gateway is offline
Most offline gateways have lost their power or internet connection. Check these first:
- Is the gateway powered? Check the status indicator and the power supply.
- Is the internet connection working? For a SIM, check that it is active, recharged and has signal. For a wired network, check the cable and ask your IT team whether anything changed.
- Was the subscription renewed? An expired subscription stops data.
The wired connection does not work
Symptom: a network cable is connected to the WAN port and its lights blink, but the web console shows that the Ethernet connection is not established.
Cause: the site network uses the same address range as the gateway's LAN port (192.168.1.x).
Solution: contact support. They will change the gateway's LAN address to a different range, such as 10.10.0.1.
The SIM card is inserted but there is no internet
Cause: the APN is not set or is wrong, the SIM has no data plan, or the signal is weak.
- Select Network & Provision > Cellular and enter the APN provided by your mobile operator. Leave Networking modes at 4G and IP type at IPv4/6.
- Select Save and reboot the gateway.
- Run diagnostics and check the Cellular section: the SIM should be detected and registered.
- If the SIM is not detected, switch off the gateway, reinsert the SIM and switch on again.
- If the signal is weak, move the antenna to a place with a clear view of the sky. You can check the signal history on the gateway's Network tab in TSC Connect.
- If the problem continues, try a SIM from another operator. Some sites have poor coverage from one operator.
The gateway goes offline every day or needs regular reboots
The gateway is not provisioned
Symptom: the Provisioning page shows that the gateway is not provisioned.
The network blocks the gateway
The time on the gateway is wrong
Solution: run diagnostics and check the RTC section. If the time is not synced, make sure the gateway can reach pool.ntp.org on port 123.
The gateway is online but no data arrives
The polling commands or port settings are wrong
The instrument does not respond
- Check that the instrument is powered on and the cable is connected at both ends.
- Run diagnostics on the gateway and check MODBUS Slave devices. "No response" or error code 101 means the instrument did not reply.
- For RS-485 instruments, check that A and B are not swapped, and that the slave address and baud rate match.
- For 4-20 mA sensors, measure the loop current with a multimeter. It should be between 4 and 20 mA. Check that the analog channel is enabled on the gateway.
- For Modbus TCP instruments, check that the instrument's IP address is reachable from the gateway. Error code 105 points to this.
- If the analyzer was replaced or reconfigured, tell support the new details.
The RS-485 port does not respond at all
Solution: remove the RS-485 connector and check it for damage, such as burn marks. If the port is damaged, contact support to arrange a repair. See
Gateway Warranty and Repairs.
The reading does not match the analyzer
Data arrives in TSC but not on the regulator portal
Related articles
- Running Diagnostics and Viewing Logs on a CloudConnect V5 Gateway – check connectivity, instruments and logs on the gateway.
- CloudConnect Gateway Error Codes – what error codes 101, 102, 103 and 105 mean.
- Data Gaps After a Network or Power Outage – what happens to data when a gateway goes offline.
- Contacting Support About a Gateway – what to have ready when you contact support.
- Gateway Firewall and Network Requirements – ports and addresses your network must allow.
- Viewing Gateway Details – check a gateway's status, ports and messages in TSC Connect.
- Setting Up Offline Alerts – get notified when an instrument stops sending data.
- Station Offline or Data Not Updating – find out whether the gateway, the analyser or the network is the cause.
- Data Not Showing on CPCB ODAMS – data is live in TSC Enviro but missing on CPCB ODAMS.
- Readings Don't Match the Analyser – units, ranges and analyser faults behind values that differ.