Checking 4-20 mA Readings and Ranges

Checking 4-20 mA Readings and Ranges

If a reading in The Sustainability Cloud does not match the value on the analyzer or local display, the cause is usually the range or scaling set for the parameter. This article shows how 4-20 mA readings are converted and how to check them.

How a 4-20 mA signal becomes a reading

A 4-20 mA analyzer sends 4 mA at the bottom of its range and 20 mA at the top. The reading is calculated as:
Reading = Range low + (Current − 4) ÷ 16 × (Range high − Range low)
For example, a pH analyzer with a range of 0–14 that sends 13.52 mA gives a reading of 0 + (13.52 − 4) ÷ 16 × 14 = 8.33 pH.
The range set in TSC Connect must match the range set on the analyzer. If someone changes the analyzer's range, the parameter in TSC Connect must be updated too, or the readings will be wrong.

Check the readings

  1. Note the range configured on the analyzer, for example 0–500 mg/Nm³.
  2. In TSC Connect, open the parameter and check that Apply Analog Scaling is on and that the scale matches the analyzer's range. See Adding a Parameter to a Field Instrument.
  3. Measure the loop current with a multimeter and work out the expected reading with the formula above. Compare it with the reading in The Sustainability Cloud.
  4. To test the gateway input itself, an instrument technician can feed known currents of 4, 8, 12 and 20 mA from a milliamp source and check that the readings match.

Other causes of wrong readings

CauseWhat to do
The analyzer was replaced or reconfiguredTell support the new make, model, range and Modbus settings so the configuration can be updated.
Wrong Modbus register, data type or byte order (for digital instruments)Check the register against the analyzer's Modbus map. See Modbus Commands for CloudConnect Gateways.
The multiplier or offset is wrongCheck the Multiplier and offset in the parameter. The formula is final = (raw × multiplier) + offset.
The plant is shut downAnalyzers can show unusual values during a shutdown or purge. Check the analyzer status before you raise a ticket.
The analog channel is not enabledTurn on the analog channel. See Configuring Polling and Ports on a CloudConnect V5 Gateway.
If you need help, send support the analyzer range, a photo of the analyzer display and the current you measured.

Related articles

  1. Connecting Meters and Sensors to a CloudConnect V5 Gateway – wire RS-485, 4-20 mA and Modbus TCP instruments.
  2. Configuring Polling and Ports on a CloudConnect V5 Gateway – set the polling interval, analog channels and RS-485 port.
  3. Troubleshooting a CloudConnect V5 Gateway – fix a gateway that is offline or not sending data.
  4. Adding a Parameter to a Field Instrument – map a register and set scaling for a parameter.
  5. Using the Instrument Configurator – configure an instrument on a gateway step by step.
  6. Readings Don't Match the Analyser – units, ranges and analyser faults behind values that differ.
  7. Requesting a Range, Unit, Factor or Limit Change – what to include so a range, unit, factor or alert limit change is done in one go.