| Check | What to look for |
| Units | Is one screen in ppm and the other in mg/Nm³, or CO in % and mg/Nm³? For example, SO2 in ppm is converted to mg/Nm³ with a factor of about 2.62. |
| 4-20 mA range | Does the range set on the analyser match the range configured for that parameter? Read the mA at the analyser output and work out the value. For example, 13.52 mA on a pH 0-14 range is pH 8.33. See Checking 4-20 mA Readings and Ranges. |
| The analyser itself | Does the analyser show the same spike, flat line or zero? If so, the analyser needs attention at site. |