Readings Don't Match the Analyser

Readings Don't Match the Analyser

TSC Enviro™ shows the values the gateway receives, without changing them. When a reading differs from the analyser display or the regulator portal, the cause is almost always one of the three below.

Symptoms

  1. The value in TSC Enviro™ or on the CPCB portal is different from the analyser at the same time.
  2. Short spikes to very high values.
  3. The value stays flat or reads zero.

Check these first

CheckWhat to look for
UnitsIs one screen in ppm and the other in mg/Nm³, or CO in % and mg/Nm³? For example, SO2 in ppm is converted to mg/Nm³ with a factor of about 2.62.
4-20 mA rangeDoes the range set on the analyser match the range configured for that parameter? Read the mA at the analyser output and work out the value. For example, 13.52 mA on a pH 0-14 range is pH 8.33. See Checking 4-20 mA Readings and Ranges.
The analyser itselfDoes the analyser show the same spike, flat line or zero? If so, the analyser needs attention at site.
Modbus (digital) parameters have no range on the TSC Enviro™ side. Their values come straight from the analyser. To see a parameter's register, data type, multiplier and offset in TSC Connect, See Viewing Parameter and Model Details.

What to send to support

  1. Industry and station name, and the parameter.
  2. Screenshots of the analyser and of TSC Enviro™ (or the portal) for the same date and time.
  3. For 4-20 mA parameters: the mA reading and the range set on the analyser.
  4. Remote access details, if you want support to look at the live signal.
If the checks above don't solve it, raise a ticket with support.

What happens next

  1. If a unit, range or factor is wrong in TSC Enviro™, LogicLadder corrects it, usually the same day. See Requesting a Range, Unit, Factor or Limit Change.
  2. If the unit on the CPCB portal is wrong, your industry changes it there, and it must match your CTO. How depends on the portal. See Requesting a Range, Unit, Factor or Limit Change.
  3. If the analyser is sending those values, support shows you the trend and your site or analyser supplier fixes the analyser.

Related articles

  1. Checking 4-20 mA Readings and Ranges – how a 4-20 mA signal becomes a reading, and how to check it.
  2. Requesting a Range, Unit, Factor or Limit Change – what to include so a range, unit, factor or alert limit change is done in one go.
  3. Viewing Parameter and Model Details – the technical details of a parameter and model.
  4. Analyser Not Sending Data – the gateway is online but one analyser or parameter has no data.