Provisioning a CloudConnect V5 Gateway and Adding It to TSC Connect

Provisioning a CloudConnect V5 Gateway and Adding It to TSC Connect

Provisioning links a gateway to your organization in The Sustainability Cloud. Until it is provisioned, the gateway cannot send data.

Before you start

  1. The gateway is installed, powered on and connected to the internet. See Initial Setup: Signing In and Connecting the Gateway to the Internet.
  2. Your network allows the gateway's traffic. See Troubleshooting a CloudConnect V5 Gateway. Your IT team can use the Gateway Firewall and Network Requirements article.
  3. You have access to TSC Connect with permission to add gateways, or you are working with LogicLadder support.

Find the MAC address

The MAC address identifies the gateway. It is shown on the Home page of the gateway's web console and on the label of the gateway, in the format xx:xx:xx:xx:xx:xx.

Add the gateway in TSC Connect

  1. Open TSC Connect and select Internet of Things (IIoT) > Gateways in the side menu. Click Here
  2. Select Add Gateway.
  3. Enter the details:
    1. MAC Address: the gateway's MAC address.
    2. Gateway Model: for example CloudConnect V500, CloudConnect V501 STD or CloudConnect V505.
    3. Data Source: IOT-Gateway.
    4. Name: a name that tells your team where the gateway is, such as the plant and stack.
    5. Serial Number and IMEI Number: optional, but they help support identify the gateway.
  4. Leave Enable device connectivity immediately off unless support tells you otherwise.
    1. When it is off, the gateway is created but stays inactive until provisioning is completed.
  5. Select Add Gateway to save. For more about this form, see Adding and Managing Gateways.
If you do not have access to TSC Connect, send the MAC address, model and location of the gateway to support, and they will add it for you.

Provision the gateway

  1. Get the provisioning PIN for the gateway from support.
  2. In the gateway's web console, select Network & Provision > Provisioning.
  3. Paste the PIN and select Save.
  4. Check that the provisioning status changes to Provisioned and the server connection status turns green.
  5. In TSC Connect, check that the gateway shows as online.
To provision a gateway again, for example after support resets it, enter the new PIN in Provisioning only. Do not delete any other configuration. An administrator can also start re-provisioning from the gateway's actions menu in TSC Connect with Re-provision.

Next steps

  1. Add your instruments in TSC Connect. See Adding a Field Instrument.
  2. Set up polling with the Configurator. See Using the Instrument Configurator.
  3. Set up offline alerts so your team knows if the gateway stops sending data. See Setting Up Offline Alerts.

Related articles

  1. Initial Setup: Signing In and Connecting the Gateway to the Internet – sign in to the web console and set up WAN, Wi-Fi or cellular.
  2. Configuring Polling and Ports on a CloudConnect V5 Gateway – set the polling interval, analog channels and RS-485 port.
  3. Running Diagnostics and Viewing Logs on a CloudConnect V5 Gateway – check connectivity, instruments and logs on the gateway.
  4. Troubleshooting a CloudConnect V5 Gateway – fix a gateway that is offline or not sending data.
  5. Adding and Managing Gateways – register a gateway in TSC Connect.
  6. Viewing Gateway Details – check a gateway's status, ports and messages in TSC Connect.
  7. Using the Instrument Configurator – configure an instrument on a gateway step by step.
  8. Setting Up Offline Alerts – get notified when an instrument stops sending data.