CloudConnect Gateway Error Codes

CloudConnect Gateway Error Codes

When the gateway polls an instrument, the instrument can reply normally, not reply, or reply with an error. These error codes can appear in the gateway's messages and logs. Support can tell you which code an instrument is returning.

Error codes

CodeMessageWhat it meansWhat to do
101Response not received for polling.The instrument did not reply. It may be switched off or disconnected, or the slave address or port settings may be wrong.Check the power, wiring, slave address and serial settings of the instrument.
102CRC Mismatched in Response.The reply was corrupted, or the polling command was not built correctly.Check the polling command and the cable, especially on long or noisy RS-485 runs.
103MODBUS Exception Received in Response.The instrument received the command but could not carry it out, for example because the register address or function code is not valid for that instrument.Check the register addresses and function code against the instrument's Modbus map.
105MODBUS TCP Socket not connected/failed.The gateway could not open a network connection to a Modbus TCP instrument.Check the instrument's IP address and port, its network cable and that it is on the same network as the gateway.

Why an instrument may not reply

  1. The instrument did not receive the command, for example because of a wiring fault.
  2. The instrument received the command with a parity, CRC or LRC error and ignored it.
  3. The instrument received the command but could not process it, and sent an exception reply (code 103).

Related articles

  1. Troubleshooting a CloudConnect V5 Gateway – fix a gateway that is offline or not sending data.
  2. Modbus Commands for CloudConnect Gateways – how Modbus RTU, TCP and ASCII polling commands are built.
  3. Running Diagnostics and Viewing Logs on a CloudConnect V5 Gateway – check connectivity, instruments and logs on the gateway.
  4. Contacting Support About a Gateway – what to have ready when you contact support.
  5. Viewing Gateway Details – check a gateway's status, ports and messages in TSC Connect.
  6. Analyser Not Sending Data – the gateway is online but one analyser or parameter has no data.