Adding a Parameter to a Field Instrument

Adding a Parameter to a Field Instrument

A parameter is a single value read from an instrument, such as CO or PM10. When you add a parameter, you choose the standard parameter and units, and map it to the Modbus register the value is read from.

Add a parameter

  1. Open the field instrument and select the Parameters tab. Click Here
  2. Click Add Parameter.
  3. Under Parameter Information, select:
    1. Parameter: the standard parameter to monitor. Search by name or label.
    2. Measurement Unit: the unit the instrument reports in.
    3. Display Unit: the unit shown to users.
  4. Under Register Mapping (required), select the Modbus register this value is read from. Each register shows its Modbus Address, Data Type, Function Code and Last Value, and is marked Available or Mapped in other device.
  5. Optionally, complete Value Processing & Display (see below).
  6. Turn on Save to Storage if the values should be kept for reporting.
  7. Under Additional Configuration, turn on the alerts and options you need.
  8. Click Add Parameter.
Can't find the register you need? Contact support@logicladder.com and the team will map it for your device model.

Value processing and display

SettingWhat it does
Apply Analog ScalingMaps a raw electrical signal (for example 4–20 mA) to engineering units on a linear scale. Required for analog ports.
MultiplierFactor applied to the raw value: final = (raw × multiplier) + offset. For example, 0.001 converts milliamperes to amperes.
Calibration ErrorKnown error from the sensor's calibration certificate, applied as a correction. Leave blank to use the model default.
PrecisionDecimal places shown, for example 2 shows 23.45.
Min Reading / Max ReadingThe lowest and highest values the sensor can measure. Values outside this range are treated as out of range.

Storage and additional options

  1. Save to Storage – forwards values to the data lake for reporting and long-term analysis.
  2. Offline Alert – sends an alert when data stops arriving.
  3. Constant Data Alert – sends an alert when the value stays the same for a long time.
  4. Allow Negative Values – accepts negative readings.
  5. Remote Calibration – available only when remote calibration is enabled for the instrument.
While Save to Storage is off, values are visible in TSC Connect for validation but are not kept for reporting. You can turn storage on at any time from the parameter list on the instrument page.

Related articles

  1. Viewing Parameter and Model Details – the technical details of a parameter or instrument model.
  2. Viewing and Updating a Field Instrument – the instrument detail page, editing and the activity timeline.
  3. Setting Up Offline Alerts – get notified when a parameter stops sending data.
  4. Checking 4-20 mA Readings and Ranges – fix readings that do not match the analyzer.