Configuring Polling and Ports on a CloudConnect V5 Gateway

Configuring Polling and Ports on a CloudConnect V5 Gateway

The Devices page in the gateway's web console holds the gateway's polling settings, analog channels and port settings. These settings are synced from TSC Connect.
The easiest way to set up polling is to add your instruments in TSC Connect and use the Configurator, which pushes the settings to the gateway and checks that data arrives. Change settings on the gateway itself only for testing or when support asks you to. You can also view and change these settings remotely. See Configuring a Gateway.

Open the device configuration

  1. Sign in to the gateway's web console. See Initial Setup: Signing In and Connecting the Gateway to the Internet.
  2. Select Devices in the side menu and wait for the configuration to sync. A success message appears.
  3. If an error appears, sync again.

General settings

SettingWhat it does
NTP ServerThe time server the gateway uses. It uses pool.ntp.org by default. You do not need to change it.
Polling intervalHow often, in seconds, the gateway reads the instruments. The default is 60 seconds.
Secure Socket LayerEncrypts the connection to the server. It is on by default. Leave it on.
ADC ChannelsThe two 4-20 mA analog inputs. They are off by default. Turn on each channel that has a sensor connected.

Port settings

  1. Check the RS-485 port settings. The port is on by default, with 9600 baud, 8 data bits, no parity and 1 stop bit. Change them to match your instruments if needed.
  2. Enter the polling commands for the port. See Modbus Commands for CloudConnect Gateways.
  3. Select Save, then restart the application so the changes take effect.
Resetting the configuration erases all settings, and the gateway must be provisioned again. Do not reset it unless support asks you to.

Related articles

  1. Modbus Commands for CloudConnect Gateways – how Modbus RTU, TCP and ASCII polling commands are built.
  2. Running Diagnostics and Viewing Logs on a CloudConnect V5 Gateway – check connectivity, instruments and logs on the gateway.
  3. Connecting Meters and Sensors to a CloudConnect V5 Gateway – wire RS-485, 4-20 mA and Modbus TCP instruments.
  4. Provisioning a CloudConnect V5 Gateway and Adding It to TSC Connect – register the gateway so it can send data to TSC.
  5. Using the Instrument Configurator – configure an instrument on a gateway step by step.
  6. Configuring a Gateway – change polling and parsing settings from TSC Connect.