Analyser Not Sending Data

Analyser Not Sending Data

Use this article when the gateway is online but one analyser or parameter has no data, freezes, or drops out often. The station usually shows Partial Live.

Check these first

  1. The analyser is powered on and shows values on its own display.
  2. For 4-20 mA outputs, measure the output. Below 4 mA is read as no signal.
  3. For Modbus outputs, read the registers with a Modbus tool. If the tool can't read them, the gateway can't either: contact your analyser supplier.
  4. Check the error code the gateway reports for that instrument, for example 101 when the instrument doesn't reply. See CloudConnect Gateway Error Codes.
  5. Check the wiring and the gateway's polling and port settings (address, baud rate, parity). See Connecting Meters and Sensors to a CloudConnect V5 Gateway, Configuring Polling and Ports on a CloudConnect V5 Gateway.
  6. Nothing was rewired, replaced or re-addressed recently.
  7. The gateway's SIM signal or network is stable. Weak signal causes frequent drop-outs; a wired line may be needed.

Replaced or new analyser?

A new analyser, or a different make or model, needs its Modbus details updated. Send the make, model, register map (or manual) and device ID. If the model isn't available yet, LogicLadder adds it, and you can then set it up in TSC Connect. See Adding an Instrument Model That Is Not Listed, Using the Instrument Configurator.

What to send to support

  1. Industry, station and parameter.
  2. Analyser make and model, and the Modbus details or 4-20 mA range.
  3. A screenshot from your Modbus tool, or the mA reading.
  4. When the data stopped, and anything changed at site.
If the checks above don't solve it, raise a ticket with support.
LogicLadder needs an active subscription to work on an industry's set-up.

What happens next

  1. Support checks what the gateway is receiving for that parameter. For some problems support connects to the gateway through a laptop at site. See Preparing for a Remote Support Session.
  2. Modbus address and model updates are usually done the same day.
  3. If the analyser isn't sending a value, your site, partner or analyser supplier repairs it.

Related articles

  1. CloudConnect Gateway Error Codes – what each instrument error code means.
  2. Troubleshooting a CloudConnect V5 Gateway – fix a gateway that is offline or not sending data.
  3. Adding an Instrument Model That Is Not Listed – what to send when your analyser model is missing.
  4. Readings Don't Match the Analyser – units, ranges and analyser faults behind values that differ.