Installing and Powering Up a CloudConnect V5 Gateway

Installing and Powering Up a CloudConnect V5 Gateway

Follow these steps to install a CloudConnect V5 gateway at your site. Read the Safety and Disposal Instructions for CloudConnect Gateways first.

Before you start

  1. Choose a location close to your instruments, with good cellular signal if you use a SIM, and away from heat sources, water and vibration.
  2. Make sure the operating temperature at the location is between 0 °C and 70 °C for V500 and V501 gateways.
  3. Keep the SIM card, the APN of your mobile operator and a laptop with an Ethernet cable ready.
  4. Complete the checklist in Preparing Your Site for a CloudConnect Gateway, and make sure your IT team has the details in Network, Firewall and SIM Requirements for CloudConnect Gateways.

Mount the gateway

  1. STD and ADV packages:
    1. Mount the IP65 enclosure on a rigid surface using four fastening screws.
    2. Connect the mains AC supply to the input of the power supply in the enclosure. The power supply output is pre-wired to the gateway.
  2. Bare Gateway:
    1. Clip the gateway onto a DIN rail inside your IP65 panel using the mounting channel.
    2. Connect a 9–30 V DC supply of at least 1 A to the DC power connector. Check the polarity before you switch on.

Place the antenna

  1. Screw the antenna cable onto the cellular antenna (SMA) connector of the gateway.
  2. Place the antenna outside the metal enclosure, with a clear view of the sky. The magnetic base holds it on metal surfaces.
  3. Keep the antenna away from power cables and large metal objects.
Antenna placement has a large effect on cellular signal. If the signal is weak inside a building, move the antenna to a window, roof or outside wall. Where there is no cellular coverage, use a wired connection or ask support about other options.

Insert the SIM card

  1. Make sure the gateway is switched off. Do not insert or remove the SIM while the gateway is powered.
  2. Insert a mini-SIM (standard size) card into the push-push SIM holder until it clicks, with the chip facing the direction marked on the gateway. To remove it, push it in again and it springs out.

Connect the network and instruments

  1. If the site provides a wired internet connection, connect it to the WAN port.
  2. Connect your instruments. See Connecting Meters and Sensors to a CloudConnect V5 Gateway.

Power up

  1. Switch on the power.
  2. The status indicator lights up. Wait about one minute for the gateway to start.
  3. Sign in to the gateway and connect it to the internet. See Initial Setup: Signing In and Connecting the Gateway to the Internet.

Related articles

  1. Safety and Disposal Instructions for CloudConnect Gateways – read before installing or servicing a gateway.
  2. Connecting Meters and Sensors to a CloudConnect V5 Gateway – wire RS-485, 4-20 mA and Modbus TCP instruments.
  3. Initial Setup: Signing In and Connecting the Gateway to the Internet – sign in to the web console and set up WAN, Wi-Fi or cellular.
  4. Provisioning a CloudConnect V5 Gateway and Adding It to TSC Connect – register the gateway so it can send data to TSC.
  5. Gateway Firewall and Network Requirements – ports and addresses your network must allow.