Preparing Your Site for a CloudConnect Gateway
Use this checklist before a CloudConnect gateway is installed. Completing it avoids repeat site visits and delays in getting data live.
Power
- For STD and ADV packages: a mains AC supply (230 V AC) at the panel location, preferably from a UPS, with a disconnect switch.
- For a bare gateway: a DC supply of 9–30 V (12–24 V is typical) that can deliver at least 1 A, connected to the correct port.
Location and mounting
- A rigid wall or panel near the instruments, away from heat, water and vibration.
- A position for the antenna with a clear view of the sky, if the gateway will use cellular.
- Cable glands sealed and cables labelled (ferruled) after installation.
Internet connection
- Cellular: an active SIM card with a data plan, the operator's APN, and good signal at the gateway location. Check the signal before installation.
- Wired: a network port near the gateway and, if the site has a firewall, the addresses and ports allowed. See Network, Firewall and SIM Requirements for CloudConnect Gateways.
Instruments
- Access to the output terminals of each analyzer or meter: RS-485, Modbus TCP or 4-20 mA.
- The make, model, slave address, serial settings and range of each instrument.
- The Modbus output of each instrument checked before the gateway is connected.
- For regulatory monitoring: one gateway for each monitoring station.
Security
- Do not connect the gateway to the plant's control network (DCS or SCADA) unless your IT and OT teams have approved it.
- Allow only the outbound connections the gateway needs.
In TSC Connect
- The IOT-Gateway data source is active. See Managing Data Sources in TSC Connect.
- Someone with access to TSC Connect is available to add the gateway and instruments, or support has the details. See Setting Up TSC Connect with the Getting Started Guide.
Related articles
- Installing and Powering Up a CloudConnect V5 Gateway – mount the gateway, place the antenna, insert the SIM and switch on.
- Network, Firewall and SIM Requirements for CloudConnect Gateways – what your IT and telecom teams need to provide.
- Safety and Disposal Instructions for CloudConnect Gateways – read before installing or servicing a gateway.
- Provisioning a CloudConnect V5 Gateway and Adding It to TSC Connect – register the gateway so it can send data to TSC.
- Setting Up TSC Connect with the Getting Started Guide – activate a data source, register a gateway and add instruments.
- Managing Data Sources in TSC Connect – activate the IOT-Gateway data source.