Using the Instrument Configurator

Using the Instrument Configurator

The Instrument Configurator sets up a Modbus field instrument remotely through a TSC gateway. The process is automated: you act only at the start, to fill in the details, and at the end, to check the live data. It usually takes 4–5 minutes plus your review time.

How it works

StepWhat happensWho
1. Fill in DetailsSelect the gateway, device model, slave address and parameters to monitor.You
2. Connect to GatewayChecks the gateway is online and reachable.System, about 10 sec
3. Pre-flight CheckChecks port availability and RS-485 compatibility.System, about 10 sec
4. Push ConfigurationWrites the Modbus register mappings to the instrument.System, about 20 sec
5. Device RebootThe instrument restarts to apply the configuration.System, about 60 sec
6. Verify Live DataReceives and checks live Modbus readings.System, 2–3 min
7. Review & ConfirmCheck the live readings and approve them.You
8. Device ActiveThe instrument is configured and streaming live data.Done

Start a configuration

  1. Select Field Instruments > Configurator in the side menu of TSC Connect. Click Here
  2. Click New Configuration, read the steps and click + Start Configuration.
  3. Under Gateway Connection, select the Gateway and Port.
  4. Under Device Details, enter:
    1. Device Name
    2. Make and Device Model
    3. Slave Address (1–247)
    4. Parameters to monitor
    5. Serial Parameters – leave the default (9600,0,0,8,1,0,0) unless your device needs different settings
  5. Click Start Configuration and follow the progress on screen.
  6. When the live readings appear, check them and confirm to complete the setup.
The instrument restarts during configuration, so its data is unavailable for about a minute. Make sure the gateway is online before you start.
The Instrument Configurator page lists each session with its device, model, gateway and port, slave address, Status, who started it and when.
If the connection drops, the configurator retries automatically. If a session fails, the error details are shown and you can start a new session.

Related articles

  1. Adding a Field Instrument – register a new instrument and connect it to a gateway.
  2. Viewing Gateway Details – ports, instruments, sessions, messages and network logs.
  3. Adding a Parameter to a Field Instrument – map a measured value to a Modbus register.
  4. Connecting Meters and Sensors to a CloudConnect V5 Gateway – wire RS-485, 4-20 mA and Modbus TCP instruments.
  5. Modbus Commands for CloudConnect Gateways – how Modbus RTU, TCP and ASCII polling commands are built.
  6. CloudConnect Gateway Error Codes – what error codes 101, 102, 103 and 105 mean.