| Code | Message | What it means | What to do |
| 101 | Response not received for polling. | The instrument did not reply. It may be switched off or disconnected, or the slave address or port settings may be wrong. | Check the power, wiring, slave address and serial settings of the instrument. |
| 102 | CRC Mismatched in Response. | The reply was corrupted, or the polling command was not built correctly. | Check the polling command and the cable, especially on long or noisy RS-485 runs. |
| 103 | MODBUS Exception Received in Response. | The instrument received the command but could not carry it out, for example because the register address or function code is not valid for that instrument. | Check the register addresses and function code against the instrument's Modbus map. |
| 105 | MODBUS TCP Socket not connected/failed. | The gateway could not open a network connection to a Modbus TCP instrument. | Check the instrument's IP address and port, its network cable and that it is on the same network as the gateway. |