Connecting Meters and Sensors to a CloudConnect V5 Gateway

Connecting Meters and Sensors to a CloudConnect V5 Gateway

A CloudConnect V5 gateway can read serial, analog and Ethernet instruments at the same time. This article explains how to connect each type.
Switch off the power before connecting instruments. Never connect a power supply to the RS-485 or 4-20 mA channels.

Instruments with an RS-485 output (Modbus RTU)

Meters, analyzers and PLCs with an RS-485 port connect to the RS-485 terminals of the gateway. The gateway acts as the Modbus master and polls each instrument in turn.
  1. Use a shielded twisted-pair cable. Connect A (+) to A (+) and B (−) to B (−).
  2. To connect several instruments, connect them one after another on the same pair of wires (a daisy chain). The maximum number of instruments for the port is shown on the gateway's Ports tab in TSC Connect.
  3. Give each instrument a unique Modbus slave address between 1 and 247.
  4. Set every instrument on the chain to the same baud rate, parity, data bits and stop bits as the gateway port. The gateway default is 9600 baud, 8 data bits, no parity, 1 stop bit.
On long cable runs, fit a termination resistor at the last instrument on the chain if the instrument manual recommends it, and earth the cable shield at one end only.

Sensors with a 4-20 mA output

The gateway has two 4-20 mA analog inputs. ADV packages add an 8-channel analog module, for 10 analog inputs in total.

Loop-powered sensors

Loop-powered (two-wire) sensors, such as many temperature, pressure and level transmitters, take their power from the 4-20 mA loop. In STD and ADV packages, use the 24 V DC output terminals in the enclosure to power the loop.

Self-powered sensors

Self-powered (four-wire) sensors have their own power supply. Connect only the signal output of the sensor to the analog input of the gateway.

ADV terminal layout

TerminalsUse
1–8Analog inputs of the 8-channel module. Each can be set for current (4-20 mA or 0-20 mA) or voltage (for example −1 to +1 V or −10 to +10 V).
9RS-485 (Modbus RTU).
10–1124 V DC output, for loop-powered sensors.
12–14Mains AC input to the power supply (88–132 V AC or 176–264 V AC).
After wiring an analog sensor, the analog channel must be enabled on the gateway. See Configuring Polling and Ports on a CloudConnect V5 Gateway.

Instruments with an Ethernet output (Modbus TCP)

Instruments that communicate using Modbus TCP connect through the gateway's Ethernet network. Connect the instrument, or the network switch it is on, to the gateway and give the instrument a fixed IP address. Support will tell you which port and IP range to use for your site.

After wiring

Add each Modbus instrument in TSC Connect and use the Configurator to set up polling. The configurator checks the gateway port, pushes the configuration and then verifies that live data arrives. Analog sensors are added in TSC Connect on the gateway's ANALOG1 or ANALOG2 port, with analog scaling set to the sensor's range. See Adding a Field Instrument, Using the Instrument Configurator and Checking 4-20 mA Readings and Ranges. If your instrument model is not listed, see Adding an Instrument Model That Is Not Listed.

Related articles

  1. Installing and Powering Up a CloudConnect V5 Gateway – mount the gateway, place the antenna, insert the SIM and switch on.
  2. Modbus Commands for CloudConnect Gateways – how Modbus RTU, TCP and ASCII polling commands are built.
  3. Configuring Polling and Ports on a CloudConnect V5 Gateway – set the polling interval, analog channels and RS-485 port.
  4. Running Diagnostics and Viewing Logs on a CloudConnect V5 Gateway – check connectivity, instruments and logs on the gateway.
  5. Adding a Field Instrument – register a meter or sensor in TSC Connect.
  6. Using the Instrument Configurator – configure an instrument on a gateway step by step.