Setting Up TSC Connect with the Getting Started Guide

Setting Up TSC Connect with the Getting Started Guide

The Getting Started guide takes you through everything needed to start receiving live data in TSC Connect. Completed steps are marked with a green tick, and when all steps are done you see Setup complete.

Open the guide

On the Home page, click Getting Started at the top right. Click Here

Step 1: Activate a data source

A data source defines how your field devices communicate with TSC Connect. No data is collected until at least one data source is activated, so this step is required before any other.
Click Manage Data Sources to activate a data source.

Step 2: Register your gateway

This step is needed only if you use a gateway as your data source. Complete the Pre-registration Checklist first:
  1. Power supply – confirm a DC 12–24 V supply is used and connected to the correct port.
  2. Internet connectivity – if you use a SIM card, check its availability and signal strength. If you use WAN, connect the cable to the WAN port and, if the local network has a firewall, whitelist the required domains and ports.
  3. Field instrument link – check the physical connection to the field instrument.
  4. Modbus output – check the Modbus output from the instrument.
Then click Register a Gateway.
If your site network has a firewall, click View whitelist details on this step to see the domains and ports your IT team must allow. The gateway cannot connect until they are whitelisted.

Step 3: Add a field instrument

After your gateway is registered and connected, add your field instruments and map them to your data source. You can do this in two ways:
  1. Manual configuration – possible, but requires Modbus protocol expertise.
  2. TSC Instrument Configurator – assisted, automated onboarding with no expertise required.
Click Add Field Instrument to continue.
Need help with onboarding? Use the support chat button at the bottom right of the page.

If you use a CloudConnect V5 gateway, complete Preparing Your Site for a CloudConnect Gateway and Installing and Powering Up a CloudConnect V5 Gateway before you register it.

Related articles

  1. Managing Data Sources in TSC Connect – choose how your devices send data.
  2. Gateway Firewall and Network Requirements – domains and ports to whitelist for gateways.
  3. Adding and Managing Gateways – add, edit or move a gateway.
  4. Adding a Field Instrument – register a new instrument and connect it to a gateway.
  5. Using the Instrument Configurator – set up a Modbus instrument remotely without Modbus expertise.
  6. Preparing Your Site for a CloudConnect Gateway – a checklist to complete before installation.
  7. Installing and Powering Up a CloudConnect V5 Gateway – mount the gateway, place the antenna, insert the SIM and switch on.
  8. Provisioning a CloudConnect V5 Gateway and Adding It to TSC Connect – register the gateway so it can send data to TSC.