| Setting | What it does |
| Apply Analog Scaling | Maps a raw electrical signal (for example 4–20 mA) to engineering units on a linear scale. Required for analog ports. |
| Multiplier | Factor applied to the raw value: final = (raw × multiplier) + offset. For example, 0.001 converts milliamperes to amperes. |
| Calibration Error | Known error from the sensor's calibration certificate, applied as a correction. Leave blank to use the model default. |
| Precision | Decimal places shown, for example 2 shows 23.45. |
| Min Reading / Max Reading | The lowest and highest values the sensor can measure. Values outside this range are treated as out of range. |