Setting Up Escalation Rules

Setting Up Escalation Rules

An escalation rule notifies more people if an alarm stays unresolved. Each alert rule can have up to five escalation levels.

Set up escalation levels

  1. Select the settings (gear) icon at the top of the page, then Alerts and Alarms > Instantaneous. Or choose Periodic.
  2. Select the three-dot icon on the alert rule and choose Escalation rule.
  3. Select Create next to Level 1.
  4. In Create Escalation Rule:
    1. Interval: how long the alarm must stay unresolved before this level is notified, in days, hours or minutes
    2. Notification frequency: how often reminders are sent at this level
    3. Escalated to: the users to notify, and any other email address
  5. Select Create.
  6. Repeat for the next level if needed.
Levels must be set up in order. You cannot create a level until the level before it is set up.
A common pattern is to notify the shift engineer at level 1, the facility manager at level 2 and the energy manager at level 3, with longer intervals at each level.